Measurement Object: LDTRPMON

 

The measurement object LDTRPMON is measuring the amount of load tripped or shed by the different loads models inside the CMPLDW and CMPLDWNF load characteristic model.

Explanation on how to insert the model with the Model Explorer is presented here.

Example of adding the LDTRPMON with an aux file:

DATA (MeasurementObjectModel_LDTRPMON, [WhoAmIMeasuring,ObjectType,DefaultData,Status,SubIntervals,DiffModified])

{

"Load '5' '1'" "LDTRPMON" "Default" "Active" "" ""

}

DATA (MeasurementObjectModel_LDTRPMON, [WhoAmIMeasuring,ObjectType,DefaultData,Status,SubIntervals,DiffModified])

{

"Area '1'" "LDTRPMON" "Default" "Active" "" ""

}

DATA (MeasurementObjectModel_LDTRPMON, [WhoAmIMeasuring,ObjectType,DefaultData,Status,SubIntervals,DiffModified])

{

"Zone '1'" "LDTRPMON" "Default" "Active" "" ""

}

 

In the Concise Variables Names and Headers format:

MeasurementObjectModel_LDTRPMON (WhoAmIMeasuring,ObjectType,DefaultData,Status,SubIntervals,DiffModified)

{

"Load '5' '1'" "LDTRPMON" "Default" "Active" "" ""

}

MeasurementObjectModel_LDTRPMON (WhoAmIMeasuring,ObjectType,DefaultData,Status,SubIntervals,DiffModified)

{

"Area '1'" "LDTRPMON" "Default" "Active" "" ""

}

MeasurementObjectModel_LDTRPMON (WhoAmIMeasuring,ObjectType,DefaultData,Status,SubIntervals,DiffModified)

{

"Zone '1'" "LDTRPMON" "Default" "Active" "" ""

}

 

The model have the following measurement outputs:

Pld-Total load active power at high side bus, MW

xshn-Nominal value of load shed, MW

xton-Nominal value of load tripped, MW

xtoi-Instantaneous value of load tripped and shed, MW

Pdg-Distributed Generation P, MW

xdgn-Nominal value of distributed generation tripped, MW

xdgi-Inst. value of distributed generation tripped and shed ,MW

Pst-Static load P, MW

Pel-Electronic load P, MW

Pma-Motor A P, MW

Pmb-Motor B P, MW

Pmc-Motor C P, MW

Pmd-Motor D P, MW

xeln-Nominal electronic load tripped, MW

xman-Nominal motor A load tripped, MW

xmbn-Nominal motor B load tripped, MW

xmcn-Nominal motor C load tripped, MW

xmdn-Nominal motor D load tripped, MW

xeli-Instantaneous electronic load tripped and shed, MW

xmai-Instantaneous motor A load tripped and shed, MW

xmb-Instantaneous motor B load tripped and shed, MW

xmci-Instantaneous motor C load tripped and shed, MW

xmdi-Instantaneous motor D load tripped and shed, MW

xst - Instantaneous static load tripped and shed, MW

where:

Instantaneous means the Initial MW value minus present MW value.

Nominal means the fraction tripped times initial MW value.

 

This model is supported in PSLF.